Shenzhen Usafe Intelligent Technology Co., Ltd
|
Price: | 40.0 USD |
Payment Terms: | T/T |
Place of Origin: | Guangdong, China (Mainland) |
Add to My Favorites | |
HiSupplier Escrow |
Features
External (key-switch operated):
Reset/resound/test zone lamps evacuate
Silence alarm sounders
Silence fault sounders
Internal:
One man detector test
Zone isolate
Revert to short-circuit: fire (no resistors in call points)
External indicators:
Sounder fault
Battery/power supply fault
Mains on
Zone fire
Zone fault
Internal indicators:
Open circuit zone fault
Short circuit zone fault
Zone isolated
Engineer test selected
Outputs:
Two sounder circuits (alarm relay contacts can be obtained by connecting a relay to a sounder circuit)
Ancillary connections for expansion modules will allow the following:
Repeater panels
Multiple sounder outputs
Connection to landlord panel
Specifications
2 (0.8A SUPPLY) | 4 / 6 (1.5A SUPPLY) | 8/10/12/14/16/18 (4.0A SUPPLY) | |
POWER SPECIFICATION | |||
MAINS SUPPLY VOLTAGE | 230V±10%Va.c.50/60Hz | 230V±10%Va.c.50/60Hz | 230V±10%Va.c.50/60Hz |
INTERNAL POWER SUPPLY | 27 Vd.c. | 27 Vd.c. | 27 Vd.c. |
TOTAL OUTPUT CURRENT LIMITED TO | 800mA@240VAC | 1500mA@240VAC | 4000mA@240VAC |
AUXILIARY POWER OUTPUT | 27 Vd.c. | 27 Vd.c. | 27 Vd.c. |
MAINS SUPPLY MONITORED FOR FAILURE | YES | YES | YES |
BATTERY CHARGER MONITORED FOR FAILURE | YES | YES | YES |
BATTERIES MONITORED FOR DISCONNECTION AND FAILURE | YES | YES | YES |
DETECTOR CIRCUIT SPECIFICATION | |||
NUMBER OF CIRCUITS | 2 | 4 or 6 | 8, 10, 12, 14,16,or 18 |
LINE FAULT MONITORED FOR OPEN CIRCUIT | YES | YES | YES |
LINE FAULT MONITORED FOR SHORT CIRCUIT | YES (Can be disabled) | YES (Can be disabled) | YES (Can be disabled) |
LINE FAULT MONITORED FOR DETECTOR REMOVAL | Yes, if End of Line Monitor Unit fitted in place of End of Line Resistor | ||
END OF LINE RESISTOR (SUPPLIED) VALUE | 6800Ω,5% tolerance,0.25W | 6800Ω,5% tolerance,0.25W | 6800Ω,5% tolerance,0.25W |
DETECTOR CONTINUITY DIODES | Silicon 1N4001 or Schottky type(required if End of Line Monitor Unit fitted to give Detector Removal Fault) | ||
CALL POINT RESISTOR VALUE (NOT SUPPLIED) | 470 to 680Ω, 0.5W | 470 to 680Ω, 0.5W | 470 to 680Ω, 0.5W |
MAXIMUM NUMBER OF SMOKE DETECTORS PER ZONE | 20(maximum detector current = 2mA) | 20(maximum detector current = 2mA) | 20(maximum detector current = 2mA) |
MAXIMUM NUMBER OF MANUAL CALL POINTS PER ZONE | No limit | No limit | No limit |
SOUNDER CIRCUIT SPECIFICATION | |||
NUMBER OF CIRCUITS | 2 | 2 | 2 |
END OF LINE RESISTOR VALUE | 6800Ω, 5%tolerance,0.25W | 6800Ω, 5%tolerance,0.25W | 6800Ω, 5%tolerance,0.25W |
LINE FAULT MONITORED FOR OPEN CIRCUIT | YES | YES | YES |
LINE FAULT MONITORED FOR SHORT CIRCUIT | YES | YES | YES |
OUTPUTS FUSED AT | 1 Amp | 1 Amp | 1.6 Amp |
MAXIMUM TOTAL OUTPUT CURRENT ALL OUTPUTS | 800mA | 1500mA | 4000mA |
MAXIMUM NO OF BELLS @ 25 mA EACH BELL | 32 | 56 | 120 |
MAXIMUM NO OF ELECTRONIC SOUNDERS @ 20 mA | 40 | 70 | 150 |
AUXILIARY RELAY CONTACTS (DO NOT CONNECT MAINS VOLTAGES) | 1A 30 Vd.c. max Voltage Free | 1A 31 Vd.c. max Voltage Free | 1A 32 Vd.c. max Voltage Free |
FUSES-ALL FUSES COMPLIANT TO IEC (EN60127 PT2) | |||
MAINS TERMINAL BLOCK | 200mA T 20 mm | 400mA T 20mm | 630mA T 20mm |
SOUNDER OUTPUTS | 1A F 20mm | 1A F 20mm | 1.6A F 20mm |
AUXILIARY OUTPUT | 1A F 20mm | 1A F 20mm | 1A F 20mm |
BATTERY FUSE | 1.6A F 20mm | 1.6A F 20mm | 3A F 20mm |
DOOR RETAINING MAGNETS | DO NOT USE PANEL POWER SUPPLY AS YOU WILL DRASTICALLY REDUCE BATTERY STAND-BY TIME | ||
CONNECTION BLOCK | |||
LARGEST ACCEPTABLE CONDUCTOR SIZE | 2.5mm2 | 2.5mm2 | 2.5mm2 |
SMALLEST ACCEPTABLE CONDUCTOR SIZE | 0.75mm2 | 0.75mm2 | 0.75mm2 |
DIMENSIONS | |||
ENCLOSURE(WIDTH x HEIGHT x DEPTH) | 415 x 265 x 100mm | 415 x 265 x 100mm | 415 x 265 x 100mm |
WEIGHT(WITHOUT BATTERIES) | 5100g | 5200g | 5500g |